The T200-80KVA is a high-power 3-phase input / 1-phase output online double-conversion UPS. It delivers 80kVA with 380VAC input and 220VAC output, using DSP digital control, IGBT + SCR devices, and dual static switches (0ms sync / <4ms non-sync). Ideal for communication centers, hospitals, CNC, SMT, IT, and large motor loads.
Dual Static Switch: 12 SCRs, 0ms sync transfer, <4ms non-sync
Online Double Conversion: Full isolation, DSP control
Intelligent Battery Management: 1A–50A charger, auto maintenance
Self-Diagnosis: 32 sensors, 200+ fault prompts
High Efficiency: 93% at full load; ECO mode ≥98%
Output Isolation Transformer: Reduces harmonics and interference
LCD Touchscreen: bilingual, 200+ status messages
Remote Monitoring: RS232 & SNMP standard
Alarm: Green normal / Yellow battery / Red maintenance
| Item | Spec |
|---|---|
| Model | T200-80KVA |
| Capacity | 80 kVA |
| Max Input Current | 128 A |
| Input | 380VAC ±20%, 3-phase + N + G, 50/60Hz ±5% |
| Input PF | >0.97 |
| Bypass | 380VAC ±15%, 0ms transfer |
| Battery | 32×12V, 384V, 180A max discharge, 432V float |
| Charging | 8–10 hrs, 1A–50A adjustable |
| Output | 220VAC ±1%, 50/60Hz ±5%, sine wave |
| THD | <3% linear, <5% non-linear |
| Overload | 110–150% for 5 min, then bypass |
| Efficiency | 93% |
| Communication | RS232 & SNMP |
| Operating Temp | 0–40°C |
| Humidity | 0–95%, non-condensing |
| Altitude | <1500m (derate 1%/100m, max 4000m) |
| Cooling | Forced ventilation |
| Noise | 55–68 dB |
| Size (D×W×H) | 1000×660×1460 mm |
| Weight | 488 kg |
| Standard | YD/T 1095-2000 |
| Optional | RS485, network management, battery testing, lightning protection |
![]() |
![]() |
![]() |
![]() |
Online double conversion: Utility → Rectifier → DC bus → Inverter → Stable AC output. Battery charges simultaneously. Five modes: Normal, Battery (0ms), Bypass (<4ms), Manual Maintenance, ECO (≥98%).
Online double conversion, auto voltage stabilization (±1%), manual voltage regulation, short circuit protection, over/under-voltage alarm, phase loss alarm, overload protection, battery low-voltage protection, ECO mode, LCD touchscreen, RS232/RS485, indicator lamps, circuit breakers, terminal block wiring.
Input/output via terminal blocks; bottom/back cable entry. Neutral wire ≥6mm². Chassis grounding per local regulations. Check connections before power-on. Never wire while energized.
Contact us today for a quote or technical datasheet.
WeChat / WhatsApp: +86 13360479957
Website: www.feixiangdapower.com
Email: snow@feixiangdapower.com